FAQ No. FAQ00754
Question
Can one sensor with a 4- to 20-mA output be
connected to two K3NX or K3TS Process Meters?
Answer
It is possible to connect two Meters.
Connect the Meters in parallel, as shown in the following diagram.

Note: The input resistance of the K3NX and
K3TS is 10 Ω. When connecting two K3NX or K3TS Process Meters, the
sensor's permissible load resistance must be 20 Ω or higher.
Calculating the Maximum Number of Connectable Meters:
Use the following equation to determine how many Meters can be connected.
Sensor's permissible load resistance > Digital Panel Meter's input
resistance × Number of Meters