FAQ No. FAQ00759
Question
What kind of wiring is best to combine a
61F-GP-N Floatless Level Controller and float switch?
Answer
Connect the float switch's contact to pins 4 and 5 of the 61F-GP-N.
The voltage and current between the 61F electrodes is only about 8 VAC and
1 mA, so it is best to use a float switch contact that is for a minimal
load.