FAQ No. FAQ00844
Question
Is it acceptable to wire
61F Floatless Level
Controller's electrode cable and power cable in the same duct?
Answer
There is a possibility of improper operation, so avoid wiring the
cables in the same duct or close together.
Since there is a weak current (about 1 mA at 8 VAC) between the 61F
Controller and the electrodes, the electrode cables can be affected by
inductive noise from the power cable and operate improperly. Also, be sure
to check that the common electrode is grounded properly.