Electronic Thermostat
last update: September 2, 2015
Model | E5L-A[] | E5L-C[] |
---|---|---|
Power supply voltage | 100 to 240 VAC, 50/60 Hz | |
Operating voltage range | 85% to 110% of the rated supply voltage | |
Power consumption | Approx. 3 VA | |
Inputs | Element-interchangeable thermistor | |
Control method | ON/OFF control | |
Control output | SPDT contacts, 250 VAC, 10 A, cosΦ = 1 (resistive load) |
SPST-NO contacts, 250 VAC, 10 A, cosΦ = 1 (resistive load) |
Setting method | Analog setting | Digital settings using keys on front panel |
Indication method | No display | LCD digital display (character height: 12 mm) |
Other functions | Setting protection (key protection) Input shift Direct/reverse operation |
|
Ambient temperature | -10 to 55°C (with no icing or condensation) | |
Ambient humidity | 25% to 85% | |
Storage temperature | -25°C to 65°C (with no icing or condensation) |
Note: Do not use the output from an Inverter as the power supply.
Model | E5L-A[] | E5L-C[] |
---|---|---|
Indication accuracy | --- | ±(1°C + 1 digit) max. *1 |
Setting accuracy | --- | ±(1°C + 1 digit) max. *1 |
Hysteresis | -30 to 20°C models: Approx. 0.5 to 2.5°C
(variable) 0 to 50°C models: Approx. 0.5 to 4°C (variable) 0 to 100°C models: Approx. 0.5 to 4°C (variable) 100 to 200°C models: Approx. 0.7 to 4°C (variable) |
1 to 9°C (in increments of 1°C) |
Repeat accuracy | 1% FS max. | --- |
Minimum scale
(standard scale) |
-30 to 20°C models and 0 to 50°C models:
5°C 0 to 100°C models and 100 to 200°C models: 10°C |
--- |
Influence of
temperature |
--- | ±((1% of PV or 2°C, whichever is greater)
+1 digit) max. |
Influence of voltage | --- | |
Influence of EMS.
(at EN61326-1) |
--- | |
Sampling period | --- | 2 s |
Insulation resistance | 100 MΩ max. (at 500 VDC) | |
Dielectric strength | 2,810 VAC, 50/60 Hz for 1 min (between charged terminals and uncharged metallic parts,
between power supply terminals and input terminals, between power supply terminals and output terminals, and between input terminals and output terminals) |
|
Vibration
(malfunction) |
Frequency of 10 to 55 Hz, 0.5-mm double amplitude for 10 min each in X, Y, and Z directions | |
Vibration
(destruction) |
Frequency of 10 to 55-Hz, 0.75-mm double amplitude for 2 h each in X, Y, and Z directions | |
Shock
(malfunction) |
150 m/s2, 3 times each in 6 directions | 100 m/s2, 3 times each in 6 directions |
Shock
(destruction) |
300 m/s2, 3 times each in 6 directions | |
Electrical life
expectancy (control output relay) |
100,000 operations min (at maximum applicable load) | |
Memory protection | --- | Non-volatile memory (100,000 write
operations) |
Weight (Thermostat) | Approx. 80 g (Thermostat only) | |
Degree of protection | Front panel: IP40, Terminals: IP00 | |
Approved standards | --- | |
Conformed standards | EN 61010-1 (IEC 61010-1), Pollution Degree 2, Overvoltage Category II | |
EMC Directives | EMI: EN61326-1 *2
Radiated EMI: EN55011 Group1 ClassA Conducted EMI: EN55011 Group1 ClassA EMS: EN61326-1 *2 Electrostatic discharge immunity: EN61000-4-2 Electromagnetic field strength immunity: EN61000-4-3 Burst noise immunity: EN61000-4-4 Conducted disturbance immunity: EN61000-4-6 Surge immunity: EN61000-4-5 Voltage dip and power interruption immunity: EN6100-4-11 |
*1. The accuracy of the accessory thermistor is not included.
*2. Industrial electromagnetic environment (EN/IEC 61326-1 Table 2)
last update: September 2, 2015