Page top

Industrial Automation

Industrial Automation

Discontinued On Mar. 2019

G3RV

Solid State Relays

G3RV

Slimmest OMRON plug-in SSR with maximum width 6.2 mm

* Information in this page is a reference that you created on the basis of information in the product catalog before the end of production, may be different from the current situation, such as goods for / supported standards options / price / features of the product. Before using, please check the compatibility and safety system.

Ratings (at an Ambient Temperature of 25°C)

Input

G3RV-SL700/500-A Series

Rated
voltage
Rated current Must operate voltage Must release voltage Input voltage
AC DC % of rated voltage
50 Hz 60 Hz
12 VDC --- --- 15 mA 10.8 V 1 V ±10%
24 VDC --- --- 12 mA 21.6 V
24 VAC/DC 20 mA 21 mA 11 mA 21.6 V
48 VAC/DC 10 mA 11 mA 6 mA 43.2 V
110 VAC 7.5 mA 8.2 mA --- 99 V
230 VAC 7.3 mA 8.6 mA --- 207 V

G3RV-SL700/500-AL Series

Rated
voltage
Rated current Must operate voltage Must release voltage Input voltage
AC DC % of rated voltage
50 Hz 60 Hz
12 VDC --- --- 15 mA 10.8 V 1 V ±10%
24 VDC --- --- 12 mA 21.6 V
24 VAC/DC 20 mA 21 mA 11 mA 21.6 V
48 VAC/DC 10 mA 11 mA 6 mA 43.2 V
110 VAC 7.5 mA 8.2 mA --- 99 V
230 VAC 7.3 mA 8.6 mA --- 207 V

G3RV-SL700/500-D Series

Rated
voltage
Rated current Must operate voltage Must release voltage Input voltage
AC DC % of rated voltage
50 Hz 60 Hz
12 VDC --- --- 8 mA 10.8 V 1 V ±10%
24 VDC --- --- 4.5 mA 21.6 V
24 VAC/DC 10.7 mA 11.1 mA 4.3 mA 21.6 V
48 VAC/DC 9.6 mA 10.2 mA 6 mA 43.2 V
110 VAC 6.8 mA 7.5 mA --- 99 V
230 VAC 6.8 mA 8.1 mA --- 207 V

Output

Item G3RV-SL700/500-A(L) G3RV-SL700/500-D
Rated load voltage AC 100 to 240 V (50/60 Hz) DC 5 to 24 V
Load voltage range AC 75 to 264 V (50/60 Hz) DC 3 to 26.4 V
Load current 0.1 to 2 A (Ta=40°C) 100 µA to 3 A (Ta=40°C)
Inrush current 30 A (60 Hz/1 cycle) 30 A (60 Hz/1 cycle)
Permissible I2t; Joule Integral
(Reference value)
15 A 2 s 9 A 2 s
Application load capacity 400 W (Output voltage: AC 200 V) 72 W (Output voltage: DC 24 V)

Characteristics

Item G3RV-SL700/500-A G3RV-SL700/500-AL G3RV-SL700/500-D
Operate time 1/2 of load power source
cycle + 1 ms max.
1 ms max. 6 ms max.
Release time 40 ms max. 20 ms max. 60 ms max.
Output ON voltage drop 1.6 V rms max. 0.9 V max.
Leakage current 5 mA max. (at 200 VAC 50/60 Hz) 10 µA max. (at 24VDC)
Insulation resistance 100 MΩ min. (at 500 VDC)
Dielectric strength AC2500V 50/60 Hz for 1 min between input and output
Vibration resistance Malfunction: 10 to 55 to 10 Hz, 0.7-mm single amplitude
Shock resistance 300m/s2
Ambient temperature Storage: -30 to +100°C (with no icing or condensation)
Operating: -30 to +55°C (with no icing or condensation)
Ambient humidity 45 to 85%RH
Weight Approx. 38 g
Pollution degree 2
Degree of protection according
to IEC 60529
IP20
Rated Impulse Withstand Voltage 4.0 kV/III
Load category LC-A DC-12
Overload Current Profile 1.5Ie 1.1Ue
5 s ON, 10 s OFF, 10 cycles
Rated insulation Voltage 240 V

Approved Standards

UL 508 (File No. E64562)

Model Input ratings Contact ratings
G3RV-SL700/500-D Series 12, 24 VDC
24, 48 VAC/DC
110, 230 VAC
24 VDC 3 A (Resistive Load) at 25°C
G3RV-SL700/500-A(L) Series 12, 24 VDC
24, 48 VAC/DC
110, 230 VAC

IEC/TUV (EN 62314)

Input ratings Contact ratings
12, 24 VDC
24, 48 VAC/DC
110, 230 VAC
24 VDC 3 A (Resistive Load)
12, 24 VDC
24, 48 VAC/DC
110, 230 VAC

Accessories

PLC Interface (for G2RV-SL700 & G3RV-SL700 series only)

Input Rated voltage 30 VAC/VDC max.
Current capacity 0.5 A per channel
2.0 A total current, power supply terminal
Characteristics Ambient temperature Operating: 0 to 55°C
Storage: - 20 to 85°C
Overvoltage category III
Pollution degree 2

Cross bars

Max current
(EN60947-7-1 section 8.3.3/1991)
32 A
Max. Voltage 400 VAC
Max. Voltage
when cutting Cross-bar without using separation plate or end-bracket
250 VAC