|
RS-232C (Recommended
Standard 232C)
RS-232C is a modem interface standard for serial communications defined by
the Electronic Industries Alliance (EIA). It defines the electrical
specifications, type, and function of the signal line, as well as the
mechanical characteristics.
RS-422 and RS-485 (Recommended Standard 422 and 485)
Both RS-422 and RS-485 are standards that specify the electrical
characteristics of a balanced differential interface between drivers and
receivers defined by the EIA, both are similar in many aspects.
RS-422 allows multiple signal receivers to connect to one driver (signal
sender) on the same bus. It does not consider multiple drivers. RS-485 is
an extension to RS-422, permitting multiple drivers with tri-state output,
and allowing for a multi-drop (party line) structure.
It is possible to transmit at a higher speed with an RS-485 compared to
the RS-232C standard, which is suitable only for transmission below 20
kbits/s.
RFI (Radio Frequency Interference)
The effect from external electromagnetic fields. A type of EMI
(Electromagnetic Interference).
Isolation
DC isolation of the input and output signals of a device.
For example, when using a thermocouple to measure the temperature within
an electric oven, isolation is used to obtain accurate measurements.
Analog Signal
A signal with a continuous amplitude.
Annunciator
A process monitoring system whereby indicators are installed on the panel
and control console to represent different stages of the process. If an
error occurs, the corresponding indicator lights and an alarm sounds to
provide notification of the error.
EMI (Electromagnetic Interference)
The effect of external electromagnetic fields on device circuits and
parts.
Impedance
Refer to Output Impedance and Input Impedance.
SSR (Solid State Relay)
Also called a non-contact relay, a solid state relay is an electronic
switch that works without any moving parts. The most common is a phototriac.
Response
Refer to Frequency Response and Step Response.
Response Time
For a step response, the response time is the time taken for a target
value, display value, or an output signal to settle within a specified
range of the final value.
(For DC output devices, it often means the time taken for the signal get
from 0% to 90%.)
Temperature Coefficient
For the ambient operating temperature of a device, the amount of
temperature change due to the ambient temperature deviating from the
reference temperature causes changes in the physical properties of the
device. The temperature coefficient is the relative change of a physical
property when the temperature is changed. (Often indicated as a percentage
of the span per unit of temperature.)
Cascade Control
Cascade control is a feedback control system that uses the output of one
controller to manipulate the set point of other controllers.
Accuracy
When using an OMRON signal generator and measurement device to take
measurements under normal operating conditions, accuracy is defined as the
difference between the ideal output and the actual output expressed as a
percentage of the output span.
Allowable Load Resistance
The range of load resistance values for which performance is given.
Common Mode Rejection Ratio
Describes how well an instrument can reject the effect of common mode
voltage entering on the input from the output. It is usually expressed in
decibels (dB). It is the ratio between the common-mode voltage on the
input terminals of the device and the differential input signals required
to achieve the same characteristics in the output signal.
Common Mode Voltage
Noise voltage caused by external induction appears at the two input
terminals. It has the same amplitude and phase at both input terminals.
The common-mode voltage is the algebraic average of the instantaneous
values of the two voltages.
Error
The difference between measured value, set value, or rated value, and the
measured or supplied true value.
Repeatability/Reproducibility
The extent to which the measurements of the same item under the same
conditions match when any or all of the following are changed; the person
who is taking the measurements, the measuring device, the location, or
time. (The degree of repeatability is usually expressed as a percentage of
the span.)
Difference Input
The difference between two input terminals when a common-mode voltage is
applied to both terminals.
Cyclic Redundancy Check (CRC)
A type of block check for data transmission. It is a popular error
checking method as it is simple to implement and has an excellent error
detecting ability.
Root-Mean-Square Value
The square root of the mean of the squares of the instantaneous values of
AC current or voltage. Also called RMS value.
Time Constant
For a first-order linear time-invariant system, the time constant is the
time taken for the step response to reach about 63% of its final value.
Frequency Response
The change in gain and phase of the steady-state output as a response to
the input frequency of a sinusoidal wave.
Output Impedance
Impedance of an active device seen from its
output terminals. Like input impedance, it can also be called output
resistance.
Output Bias
Output value when the product is idle (i.e., when the input is at the
minimum value or there is no input).
For example, if the output is 1 to 5 V, 1 V is the output bias. If the
output is 0 to 5 V, 0 V is the output bias.
Signal
Refer
to Analog Signal and Digital Signal.
Step Response
Response of a system to an instantaneous change in input from one constant
value to another.
Span
Difference between the maximum and minimum values of a range. For example,
if the range is -15 to 100°C, the span is 115°C.
Split Control
Controlling two or more different elements with one control signal.
For example, for a system that controls hot water temperature with
separate control valves for hot and cold water, if both valve position
motors are set at 0% to 50%, the hot water valve is controlled open at
100% to 0% but the cold water valve remains at 0%. If the setting is at
50% to 100%, the hot water valve remains at 0% and the cold water valve is
controlled open at 0% to 100%.
Control
Refer to Cascade Control, Split Control, PID Control.
Insulation Resistance
The electrical resistance between two conductors separated by insulating
material. The electrical resistance between inputs, outputs, and power
source circuits is often of concern for electrical measurements.
Zero Elevation
Shifting the measurement range to the positive direction is called zero
elevation.
For example, if the measurement range is -25 to +100°C, zero elevation is
25°C.
Zero Suppression
Shifting the measurement range to the negative direction is called zero
suppression.
For example, if the measurement range is 0.2 to 1.0 kgf/cm², the zero
suppression is 0.2 kgf/cm².
Zero Bias
Zero-suppression and zero-elevation together is called zero bias.
(Generally it means that the bias is zero.)

Resistance Temperature Sensor
A temperature sensor that uses a resistor element which varies in
resistance depending on the temperature. The resistor element may be made
from platinum, nickel, or bronze. The platinum type is common used for
measurements in the temperature range between -200 and 650°C. In addition
to the two-wire configuration, there are three-wire and four-wire
configurations to compensate the lead-wire resistances. The three-wire
configuration has one line connected to one end of the resistor and two on
the other, and the four-wire configuration has two lines connected on
either terminals of the resistor.
Time Sharing
A technique used to run two or more processes concurrently with one
processor by alternating the run time.
Dielectric Strength/Withstand Voltage
The amount of voltage the insulation of an electrical device can withstand
in a fixed period of time.
Neutral Zone
The area between the two set points of a three-position switch.
Linearity
The degree of deviation from a linear relationship between input and
output signals. (The degree of linearity is generally indicated as a
percentage of the span.)
Digital Signal
Signals that express numbers in a discrete state.
Electric Power
The amount of work done by electricity in one unit of time. In other
words, the amount of electrical energy consumed in one unit of time.
Refer to Reactive Power, Apparent Power, and Active Power.
Input
Refer to Differential Input and Floating Input.
Input Impedance
Impedance of an active device seen from its input terminals. Often
indicated by the equivalent impedance of the parallel resistance and
capacitance. For DC measuring devices it is simply called input
resistance.
Thermocouple
A thermocouple is a type of temperature sensor that uses two conductors of
different metals that generate a voltage across its junction due to the
thermoelectric effect. The potential difference across the junction
corresponds to the temperature at the measuring junction (thermocouple
junction) compared to the temperature at the reference junction (also
known as the cold junction), which is held at a constant temperature
(e.g., 0°C). The potential difference depends on the type of metals used
in addition to the difference in temperatures at the junctions. Common
types of thermocouples are R (platinum / platinum rhodium), K (chromel /
alumel), E (chromel / constantan), and T (copper /constantan).

Normal Mode Rejection Ratio
Describes how well an instrument can reject the effect of normal mode
voltage entering on the input from the output. It is usually expressed in
decibels (dB). It is the ratio between the normal-mode voltage on the
input terminals of the device and the increase required in the input
signals to achieve the same characteristics in the output signal.
Normal Mode Voltage
Undesirable input voltage superimposed on the measurement voltage, such as
potential difference of the measuring conductors or induction voltage.
Also called series mode voltage.
Burnout (Protection)
When there is no input, the output is increased or decreased, to whichever
way is safe.
For example, when temperature is controlled using a thermocouple as the
sensor, if the thermocouple breaks down due to a burnout, the input is cut
off. When this is detected, it may be incorrectly determined as a
temperature drop, resulting in the heat controller increasing the
temperature and causing overheating. By implementing a burnout protection
function, this kind of overheating can be prevented.
Byte
A group of adjacent bits treated as one unit. Often consists of 8 bits.
Bus
A signal communications line where many devices share the same connection.
Data can be transferred from any of the signal sources to any of the
receivers connected to the bus.
GP-IB
One of the buses established by IEEE-USA. IEEE-488
VME Bus
One of the buses established by IEEE-USA. IEEE-1014
Multibus
One of the buses established by IEEE-USA. IEEE-796
Parity Check
A parity bit is added to a data set as a binary digit to indicate whether
the number of ones in a given set of bits is even or odd. It acts as an
error detecting code.
Proportional Plus Integral Plus Derivative Control
(PID Control)
A control loop that uses signals proportional to the linear combination of
the input, the time integral of the input, and the time derivative of the
input to control the output.
Binary Coded Decimal (BCD)
Each digit of a decimal number is represented by four binary bits. For
example, decimal number 23 would be expressed as 0010 0011.
Hysteresis
Properties of equipment and devices where the output value depends on the
immediately preceding history of the applied input.
Apparent Power
Apparent power is the simple product of voltage and current supplied to an
AC device and is expressed in VA (volt-amperes). It describes the ability
of AC devices and power sources to supply current at a given voltage to
transformers and motors.
Bit
Short for "binary digit". It is either 1 or 0, and refers to a digit in a
binary numeral system. It is the smallest unit of information.
Proportional Band
The range of change in the input (%) required for the output to go from 0%
to 100% during proportional action.
Load Resistance
Refer to Tolerated Load Resistance.
Dead Band
The range of input variations where the no change is detected in the
output variable. This characteristic is also called the neutral zone.
Frame
In a multiplex structure, a message is transmitted using a timesharing
method. Under this arrangement, a frame is a set of consecutive pulse
signals conveying the information on the transmission line.
Floating Input
Input terminals that are isolated from the outer casing, power source, and
various output terminals (JIS definition).
Negative Logic
There are two ways to assign high and low voltage levels and to the
information bits 0 and 1. One is to make 0 correspond to low, and 1 to
high, which is called positive logic. The other is in reverse, where 0
corresponds to high and 1 to low, which is called negative logic.
Compensating Lead Wire
An insulated pair of conductors with similar properties to the
thermocouple is connected between the thermocouple terminals and the
reference junction to compensate for measurement errors caused by
temperature change at the thermocouple terminals.
Reactive Power
The portion of power supply (apparent power) that is actually used by an
AC machine is the active power, and the portion of power due to stored
energy, which returns to the source in each cycle, is known as reactive
power. The unit for reactive power is Var.
It is the product of the voltage and current flowing in the device
multiplied by the sine value of the phase difference (θ).
Reactive power Q = Voltage E × Current I × Reactive ratio sinθ
(Var)
and
Active power P² + Reactive power Q² = Apparent power S²
Active Power
The portion of the power supply that is used by an AC machine is called
active power, in units of W (watts). It is the product of voltage,
current, and the cosine value of the phase difference (θ). The value cosθ
is referred as the power ratio, meaning the portion of power that is
useful.
Power Factor
When AC voltage E is applied to a load (the device), the phase of the AC
current I flowing in it generally lags behind the voltage E by amount θ.
More specifically, when the load is purely resistive, there is no phase
shift. When the load is inductive (i.e. a coil), it lags by θ. When the
load is capacitive (i.e. a condenser), it leads by θ.
Linearizer
For example with a thermocouple, a detection signal (mV) which has a
non-linear relationship with the measurement (temperature) can be used as
an input. A linearizer takes this signal and converts it into an output
signal that is proportional (linear relationship) to the measured value.

Relay Contact
• Make contact
(normally open (NO) contact)
•
Break contact
(normally closed (NC) contact)
•
Transfer contact
(double-throw contact)
Made from two contacts, one normally open contact and one normally closed
contact with a common terminal.
Cold Junction Compensation
Also called reference junction compensation. When measuring temperature
using thermocouples, the reference terminal may not be held at 0°C, but at
the surrounding temperature of T1°C instead. Without any compensation, the
thermocouple output will be reduced by T1°C. This is compensated by adding
potential difference to the internal amplifier corresponding to T1°C.

Range
The difference between minimum and maximum values that an input or output
can reach.
Load Cell
A load cell is a sensor that detects load or force. A strain gauge is a
commonly used type of load cell.
• Bridge Resistance
The standard resistance seen from the load cell input/output terminals
(AB/CD) at ambient temperature. Normally 350 Ω.
• Excitation Voltage
Supply voltage applied across the load cell bridge resistance (A-B),
normally 5 or 10 V.
• Rated Output
Voltage
The voltage output when the maximum load corresponding to an additional 1
V is applied to the load cell. Normally 2 mV/V.
Reference Material for Digital Panel Meters
Measuring High DC Currents
For some OMRON products, shunt resistors are used in the input section to
convert a DC current to a DC voltage to measure high DC voltages when the
measurement range is exceeded (e.g., 2 A).

Measuring DC Voltages
To measure a DC current that exceeds the measurement range of the OMRON
product, install an external voltage dividing circuit to divide the
voltage.

Measuring High AC Currents
To measure an AC current that exceeds the measurement range of the OMRON
product, install an external current transformer (CT) to reduce the
current flow. Also, install an external CT transducer to convert a DC
voltage to a DC current signal for measurement.

Measuring High AC Voltages
To measure an AC voltage that exceeds the measurement range of the OMRON
product, install an external power transformer (PT) to reduce the voltage.
Also, install a PT transducer to convert a DC voltage to a DC current
signal for measurement.

Measuring Other Forms of Signals, Sensor Signals,
and Non-linear Signals
To measure anything related to electrical output, such as power, reactive
power, power factor, frequency or phase, any signals from sensors, or any
non-linear signals, install a power transducer or a signal converter to
convert DC voltage into DC current.
|
Power |
K3FL-W[][] |
|
Reactive power |
K3FL-Q[][] |
|
Power
factor |
K3FL-C[][] |
|
Frequency |
K3FL-F[][] |
|
Phase |
K3FL-P[][] |
|
Load
cell |
K3FK-G/GS |
|
Non-linear signal |
K3FK-X |
Summary of Element Symbols
|
Element |
Symbol |
Details
|
|
Denotation in product catalogs |
Denotation by JIS |
|
NO
contact |
 |
 |
Contacts are open when the relay is inactive. |
|
NC
contact |
 |
 |
Contacts are closed when relay is inactive. |
|
Double-throw
contact |
 |
 |
Transfer contacts (also called double-throw contacts) control two
circuits, one normally open contact and one normally closed contact
with a common terminal. |
|
Diode |
 |
 |
|
|
Photocoupler |
 |
 |
|
|
AC
power source |
 |
 |
|
|
DC
power source |
 |
 |
|
|
NPN
transistor |
 |
 |
|
|
PNP
transistor |
 |
 |
|
|
Zener diode |
 |
 |
|
Parameter Display
The following symbols are used to represent the characters for parameter
names on a Digital Panel Meter.

<< What is Digital Panel Indicators?
Recommended Products

|
Temperature Indicator
K3HB-H
High-precision and capable of
high-speed sampling at 50 times per second (20 ms).
|
|

|
Weighing Indicator
K3HB-V
Ideal for OK/NG judgments in automated
and picking machines, measuring factors such as pressure, load,
torque, and weight using load cell signal input. |

|
Process Indicator
K3HB-X
Ideal for discriminating and
displaying measurements for voltage/current signals. |
|