NX-series Pulse Output Unit
last update: February 6, 2020
Item | Specification | |
---|---|---|
Enclosure | Mounted in a panel | |
Grounding method | Ground to less than 100 Ω | |
Operating
environment |
Ambient operating
temperature |
0 to 55°C |
Ambient operating
humidity |
10% to 95% (with no condensation or icing) | |
Atmosphere | Must be free from corrosive gases. | |
Ambient storage
temperature |
-25 to 70°C (with no condensation or icing) | |
Altitude | 2,000 m max. | |
Pollution degree | Pollution degree 2 or less: Meets IEC 61010-2-201. | |
Noise immunity | Conforms to IEC61000-4-4, 2 kV (power supply line) | |
Overvoltage category | Category II: Meets IEC 61010-2-201. | |
EMC immunity level | Zone B | |
Vibration resistance | Conforms to IEC 60068-2-6.
5 to 8.4 Hz with 3.5-mm amplitude, 8.4 to 150 Hz, acceleration of 9.8 m/s2, 100 min each in X, Y, and Z directions (10 sweeps of 10 min each = 100 min total) |
|
Shock resistance | Conforms to IEC 60068-2-27. 147 m/s2, 3 times each in X, Y, and Z directions | |
Applicable standards * | cULus: Listed (UL508) or Listed (UL 61010-2-201), ANSI/ISA 12.12.01,
EU: EN 61131-2, C-Tick or RCM, KC Registration, NK, LR |
* Ask your OMRON representative for the most recent applicable standards for each model.
Unit name | Pulse Output Unit | Model | NX-PG0112 | |
---|---|---|---|---|
Number of axes | 1 | Type of external
connections |
Screwless clamping terminal
block (16 terminals) |
|
I/O refreshing method *1 | Synchronous I/O refreshing or task period prioritized refreshing | |||
Indicators | ![]() |
I/O signals | Inputs: 2, External inputs
Outputs: 3, The outputs are the forward direction pulse output, reverse direction pulse output, and external output (one of each output). |
|
Control method | Open-loop control through pulse string output | |||
Controlled drive | Servo drive with a pulse string input or a stepper motor drive | |||
Pulse output form | Open collector output | |||
Control unit | Pulses | |||
Maximum pulse output
speed |
500kpps | |||
Pulse output method | Forward/reverse direction pulse outputs or pulse + direction outputs | |||
Position control range | -2,147,483,648 to 2,147,483,647 pulses | |||
Velocity control range | 1 to 500,000 pps | |||
Positioning *2 | ||||
Single-axis position
control |
Absolute positioning, relative positioning, and interrupt feeding | |||
Single-axis velocity
control |
Velocity control (velocity feeding in Position Control Mode) | |||
Single-axis
synchronized control |
Cam operation and gear operation | |||
Single-axis manual
operation |
Jogging | |||
Auxiliary function for
single-axis control |
Homing, stopping, and override changes | |||
External input specifications | ||||
Input voltage | 20.4 to 28.8 VDC
(24 VDC +20%/-15%) |
ON voltage/
ON current |
15 VDC min./3 mA min. | |
Input current | 4.6 mA typical (24 VDC) | OFF voltage/OFF
current |
4.0 VDC max./1 mA max. | |
ON/OFF response time | 1 μs max./2 μs max. | |||
Internal I/O common
processing |
NPN | |||
Pulse output and external output specifications | ||||
Rated voltage | 24 VDC | |||
Load voltage range | 15 to 28.8 VDC | Residual voltage | 1.0 V max. | |
Maximum load current | 30mA | Leakage current | 0.1 mA max. | |
ON/OFF response time | Pulse output: Refer to “NX-series Position Interface Units User’s Manual (W524-E1)”.
External output: 5 μs max./5 μs max. |
|||
Internal I/O common
processing |
NPN | |||
Dimensions | 12 × 100 × 71 mm
(W×H×D) |
Isolation
method |
External inputs:
Photocoupler isolation External outputs: Digital isolator |
|
Insulation resistance | 20 MΩ min. between isolated
circuits (at 100 VDC) |
Dielectric
strength |
510 VAC between isolated
circuits for 1minute with leakage current of 5 mA max. |
|
I/O power supply source | Supplied from the NX bus.
20.4 to 28.8 VDC (24 VDC +20%/-15%) |
Current capacity
of I/O power supply terminals |
IOV: 0.1 A max. per terminal
IOG: 0.1 A max. per terminal |
|
NX Unit power
consumption |
• Connected to a CPU Unit
1.15 W max. • Connected to a Commu- nications Coupler Unit 0.80 W max. |
Current
consumption from I/O power supply |
20 mA max. | |
Weight | 70 g max. | Cable length | 3 m max. | |
Circuit layout | ![]() |
|||
Installation orientation
and restrictions |
Installation orientation:
• Connected to a CPU Unit: Possible in upright installation. • Connected to a Communications Coupler Unit: Possible in 6 orientations. Restrictions: There are no restrictions. |
|||
Terminal connection
diagram |
![]() |
|||
Failure detection | None | Protection | None |
Unit name | Pulse Output Unit | Model | NX-PG0122 | |
---|---|---|---|---|
Number of axes | 1 | Type of external
connections |
Screwless push-in terminal
block (16 terminals) |
|
I/O refreshing method *1 | Synchronous I/O refreshing or task period prioritized refreshing | |||
Indicators | ![]() |
I/O signals | Inputs: 2, External inputs *2
Outputs: 3, The outputs are the forward direction pulse output, reverse direction pulse output, and external output *3 (one of each output). |
|
Control method | Open-loop control through pulse string output | |||
Controlled drive | Servo drive with a pulse train input or a stepper motor drive | |||
Pulse output form | Open collector output | |||
Control unit | Pulses | |||
Maximum pulse output
speed |
500kpps | |||
Pulse output method | Forward/reverse direction pulse outputs or pulse + direction outputs | |||
Position control range | -2,147,483,648 to 2,147,483,647 pulses | |||
Velocity control range | 1 to 500,000 pps | |||
Positioning *2 | ||||
Single-axis position
control |
Absolute positioning, relative positioning, and interrupt feeding | |||
Single-axis velocity
control |
Velocity control (velocity feeding in Position Control Mode) | |||
Single-axis
synchronized control |
Cam operation and gear operation | |||
Single-axis manual
operation |
Jogging | |||
Auxiliary function for
single-axis control |
Homing, stopping, and override changes | |||
External input specifications | ||||
Input voltage | 20.4 to 28.8 VDC
(24 VDC +20%/-15%) |
ON voltage/
ON current |
15 VDC min./3 mA min. | |
Input current | 4.6 mA typical (24 VDC) | OFF voltage/OFF
current |
4.0 VDC max./1 mA max. | |
ON/OFF response time | 1 μs max./2 μs max. | |||
Internal I/O common
processing |
PNP | |||
External output specifications | ||||
Rated voltage | 24 VDC | |||
Load voltage range | 15 to 28.8 VDC | Residual voltage | 1.0 V max. | |
Maximum load current | 30mA | Leakage current | 0.1 mA max. | |
ON/OFF response time | Pulse output: Refer to “NX-series Position Interface Units User’s Manual (W524-E1)”.
5 μs max./5 μs max. |
|||
Internal I/O common
processing |
PNP | |||
Dimensions | 12 × 100 × 71 mm
(W×H×D) |
Isolation
method |
External inputs:
Photocoupler isolation External outputs: Digital isolator |
|
Insulation resistance | 20 MΩ min. between isolated
circuits (at 100 VDC) |
Dielectric
strength |
510 VAC between isolated
circuits for 1minute with leakage current of 5 mA max. |
|
I/O power supply source | Supplied from the NX bus.
20.4 to 28.8 VDC (24 VDC +20%/-15%) |
Current capacity
of I/O power supply terminals |
IOV: 0.1 A max. per terminal
IOG: 0.1 A max. per terminal |
|
NX Unit power
consumption |
• Connected to a CPU Unit
1.30 W max. • Connected to a Commu- nications Coupler Unit 0.90 W max. |
Current
consumption from I/O power supply |
20 mA max. | |
Weight | 70 g max. | Cable length | 3 m max. | |
Circuit layout | ![]() |
|||
Installation orientation
and restrictions |
Installation orientation:
• Connected to a CPU Unit: Possible in upright installation. • Connected to a Communications Coupler Unit: Possible in 6 orientations. Restrictions: There are no restrictions. |
|||
Terminal connection
diagram |
![]() |
|||
Failure detection | None | Protection | None |
Unit name | Pulse Output Unit | Model | NX-PG0232-5 | |
---|---|---|---|---|
Number of channels | 2 channels | Type of external
connections |
MIL connector (34 terminals ×1) | |
I/O refreshing method *1 | Synchronous I/O refreshing or task period prioritized refreshing | |||
Indicators | ![]() |
I/O signals | Inputs: 5 per channel. External
inputs *2 Outputs: 5 per channel. 1 forward direction pulse output, 1 reverse direction pulse output, and 3 external outputs (per channel) *3 |
|
Control method | Open-loop control through pulse string output | |||
Controlled drive | Servo drive with a pulse string input or a stepper motor drive | |||
Pulse output form | Line driver output | |||
Unit of control | Pulses | |||
Maximum pulse output
speed |
4 Mpps | |||
Pulse output method | Forward/reverse direction pulse outputs, Pulse + direction outputs, or Phase differential
pulse output multiplication x1/2/4 |
|||
Position control range | -2,147,483,648 to 2,147,483,647 pulses | |||
Velocity control range | 1 to 4,000,000 pps | |||
Positioning *4 | ||||
Single-axis position
control |
Absolute positioning, relative positioning, and interrupt feeding | |||
Single-axis velocity
control |
Velocity control (velocity feeding in Position Control Mode) | |||
Single-axis
synchronized control |
Cam operation and gear operation | |||
Single-axis manual
operation |
Jogging | |||
Auxiliary function for
single-axis control |
Homing, stopping, and override changes | |||
External input specifications (except for line receiver inputs) | ||||
Input voltage | 21.6 to 26.4 VDC
(24 VDC +10%, -10%) |
ON voltage/
ON current |
15 VDC min./3 mA min. | |
Input current | 4.6 mA typical (24 VDC) | OFF voltage/OFF
current |
4.0 VDC max./1 mA max. | |
ON/OFF response time | External inputs 0 and 1: 1 μs max./2 μs max.
External inputs 2 to 4: 20 μs max./400 μs max. |
|||
Internal I/O common
processing |
NPN | |||
External input specifications (line receiver inputs) | ||||
Input voltage | EIA standard RS-422-A line
driver levels |
High level input voltage | VIT+: 0.1 V min. | |
Input impedance | 120 Ω ± 5% | Low level input voltage | VIT-: -0.1 V max. | |
Hysteresis voltage | Vhys (VIT+ - VIT-): 60 mV | |||
Line driver output specifications | ||||
Output voltage | RS-422-A line driver level (equivalent to AM26C31) | |||
Maximum load current | 20 mA | |||
Maximum output
frequency |
4 Mpps | |||
External output specifications | ||||
Rated voltage | 24 VDC | |||
Load voltage range | 15 to 28.8 VDC | Residual voltage | 1.0 V max. | |
Maximum load current | 30mA | Leakage current | 0.1 mA max. | |
ON/OFF response time | External output 0: 5 μs max./5 μs max.
External outputs 1 and 2: 0.5 ms max./1 ms max. |
|||
Internal I/O common
processing |
NPN | |||
Dimensions |
30 × 100 × 71 mm (W×H×D) |
Isolation
method |
External inputs: Photocoupler
isolation External outputs: Digital isolator |
|
Insulation resistance | 20 MΩ min. between isolated
circuits (at 100 VDC) |
Dielectric
strength |
510 VAC between isolated circuits
for 1 minute at a leakage current of 5 mA max. |
|
I/O power supply source |
Supply from external source
(24 VDC +20%, -15%) |
Current capacity
of I/O power supply terminals |
Without I/O power supply terminals | |
NX Unit power
consumption |
• Connected to a CPU Unit
1.55 W max. • Connected to a Communi- cations Coupler Unit 1.20 W max. |
Current
consumption from I/O power supply |
50 mA max. | |
Weight | 110 g max. | Cable length | Line driver outputs: 10 m max.
Other I/O: 3 m max. |
|
Circuit layout | ![]() |
|||
Installation orientation
and restrictions |
Installation orientation:
• Connected to a CPU Unit: Possible in upright installation. • Connected to a Communications Coupler Unit: Possible in 6 orientations. Restrictions: The number of external inputs that can be always ON is restricted as shown below. ![]() |
|||
Terminal connection
diagram |
![]() |
|||
Failure detection | None | Protection | None |
Unit name | Pulse Output Unit | Model | NX-PG0242-5 | |
---|---|---|---|---|
Number of channels | 2 channels | Type of external
connections |
MIL connector (34 terminals ×1) | |
I/O refreshing method *1 | Synchronous I/O refreshing or task period prioritized refreshing | |||
Indicators | ![]() |
I/O signals | Inputs: 5 per channel. External
inputs *2 Outputs: 5 per channel. 1 forward direction pulse output, 1 reverse direction pulse output, and 3 external outputs (per channel) *3 |
|
Control method | Open-loop control through pulse string output | |||
Controlled drive | Servo drive with a pulse string input or a stepper motor drive | |||
Pulse output form | Line driver output | |||
Unit of control | Pulses | |||
Maximum pulse output
speed |
4 Mpps | |||
Pulse output method | Forward/reverse direction pulse outputs, Phase + direction outputs, or Phase differential
pulse output multiplication x1/2/4 |
|||
Position control range | -2,147,483,648 to 2,147,483,647 pulses | |||
Velocity control range | 1 to 4,000,000 pps | |||
Positioning *4 | ||||
Single-axis position
control |
Absolute positioning, relative positioning, and interrupt feeding | |||
Single-axis velocity
control |
Velocity control (velocity feeding in Position Control Mode) | |||
Single-axis
synchronized control |
Cam operation and gear operation | |||
Single-axis manual
operation |
Jogging | |||
Auxiliary function for
single-axis control |
Homing, stopping, and override changes | |||
External input specifications (except for line receiver inputs) | ||||
Input voltage | 21.6 to 26.4 VDC
(24 VDC +10%, -10%) |
ON voltage/
ON current |
15 VDC min./3 mA min. | |
Input current | 4.6 mA typical (24 VDC) | OFF voltage/OFF
current |
4.0 VDC max./1 mA max. | |
ON/OFF response time | External inputs 0 and 1: 1 μs max./2 μs max.
External inputs 2 to 4: 20 μs max./400 μs max. |
|||
Internal I/O common
processing |
PNP | |||
External input specifications (line receiver inputs) | ||||
Input voltage | EIA standard RS-422-A line
driver levels |
High level input voltage | VIT+: 0.1 V min. | |
Input impedance | 120 Ω ± 5% | Low level input voltage | VIT-: -0.1 V max. | |
Hysteresis voltage | Vhys (VIT+ - VIT-): 60 mV | |||
Line driver output specifications | ||||
Output voltage | RS-422-A line driver level (equivalent to AM26C31) | |||
Maximum load current | 20 mA | |||
Maximum output
frequency |
4 Mpps | |||
External output specifications | ||||
Rated voltage | 24 VDC | |||
Load voltage range | 15 to 28.8 VDC | Residual voltage | 1.0 V max. | |
Maximum load current | 30mA | Leakage current | 0.1 mA max. | |
ON/OFF response time | External output 0: 5 μs max./200 μs max.
External outputs 1 and 2: 0.5 ms max./1 ms max. |
|||
Internal I/O common
processing |
PNP | |||
Dimensions |
30 × 100 × 71 mm (W×H×D) |
Isolation
method |
External inputs: Photocoupler
isolation External outputs: Digital isolator |
|
Insulation resistance | 20 MΩ min. between isolated
circuits (at 100 VDC) |
Dielectric
strength |
510 VAC between isolated circuits
for 1 minute at a leakage current of 5 mA max. |
|
I/O power supply source |
Supply from external source
(24 VDC +20%, -15%) |
Current capacity
of I/O power supply terminals |
Without I/O power supply terminals | |
NX Unit power
consumption |
• Connected to a CPU Unit
1.55 W max. • Connected to a Commu- nications Coupler Unit 1.20 W max. |
Current
consumption from I/O power supply |
50 mA max. | |
Weight | 110 g max. | Cable length | Line driver outputs: 10 m max.
Other I/O: 3 m max. |
|
Circuit layout | ![]() |
|||
Installation orientation
and restrictions |
Installation orientation:
• Connected to a CPU Unit: Possible in upright installation. • Connected to a Communications Coupler Unit: Possible in 6 orientations. Restrictions: The number of external inputs that can be always ON is restricted as shown below. ![]() |
|||
Terminal connection
diagram |
![]() |
|||
Failure detection | None | Protection | None |
Unit name | Pulse Output Unit | Model | NX-PG0332-5 | |
---|---|---|---|---|
Number of channels | 4 channels | Type of external
connections |
MIL connector (34 terminals ×2) | |
I/O refreshing method *1 | Synchronous I/O refreshing or task period prioritized refreshing | |||
Indicators | ![]() |
I/O signals | Inputs: 5 per channel. External
inputs*2 Outputs: 5 per channel. 1 forward direction pulse output, 1 reverse direction pulse output, and 3 external outputs (per channel)*3 |
|
Control method | Open-loop control through pulse string output | |||
Controlled drive | Servo drive with a pulse string input or a stepper motor drive | |||
Pulse output form | Line driver output | |||
Unit of control | Pulses | |||
Maximum pulse output
speed |
4 Mpps | |||
Pulse output method | Forward/reverse direction pulse outputs, Pulse + direction outputs, or Phase
differential pulse output multiplication x1/2/4 |
|||
Position control range | -2,147,483,648 to 2,147,483,647 pulses | |||
Velocity control range | 1 to 4,000,000 pps | |||
Positioning *4 | ||||
Single-axis position
control |
Absolute positioning, relative positioning, and interrupt feeding | |||
Single-axis velocity
control |
Velocity control (velocity feeding in Position Control Mode) | |||
Single-axis
synchronized control |
Cam operation and gear operation | |||
Single-axis manual
operation |
Jogging | |||
Auxiliary function for
single-axis control |
Homing, stopping, and override changes | |||
External input specifications (except for line receiver inputs) | ||||
Input voltage | 21.6 to 26.4 VDC
(24 VDC +10%, -10%) |
ON voltage/
ON current |
15 VDC min./3 mA min. | |
Input current | 4.6 mA typical (24 VDC) | OFF voltage/OFF
current |
4.0 VDC max./1 mA max. | |
ON/OFF response time | External inputs 0 and 1: 1 μs max./2 μs max.
External inputs 2 to 4: 20 μs max./400 μs max. |
|||
Internal I/O common
processing |
NPN | |||
External input specifications (line receiver inputs) | ||||
Input voltage | EIA standard RS-422-A line
driver levels |
High level input voltage | VIT+: 0.1 V min. | |
Input impedance | 120 Ω ± 5% | Low level input voltage | VIT-: -0.1 V max. | |
Hysteresis voltage | Vhys (VIT+ - VIT-): 60 mV | |||
Line driver output specifications | ||||
Output voltage | RS-422-A line driver level (equivalent to AM26C31) | |||
Maximum load current | 20 mA | |||
Maximum output
frequency |
4 Mpps | |||
External output specifications | ||||
Rated voltage | 24 VDC | |||
Load voltage range | 15 to 28.8 VDC | Residual voltage | 1.0 V max. | |
Maximum load current | 30mA | Leakage current | 0.1 mA max. | |
ON/OFF response time | External output 0: 5 μs max./200 μs max.
External outputs 1 and 2: 0.5 ms max./1 ms max. |
|||
Internal I/O common
processing |
NPN | |||
Dimensions |
30 × 100 × 71 mm (W×H×D) |
Isolation
method |
External inputs: Photocoupler
isolation External outputs: Digital isolator |
|
Insulation resistance | 20 MΩ min. between isolated
circuits (at 100 VDC) |
Dielectric
strength |
510 VAC between isolated circuits
for 1 minute at a leakage current of 5 mA max. |
|
I/O power supply source |
Supply from external source
(24 VDC +20%, -15%) |
Current capacity
of I/O power supply terminals |
Without I/O power supply terminals | |
NX Unit power
consumption |
• Connected to a CPU Unit
1.65 W max. • Connected to a Communi- cations Coupler Unit 1.30 W max. |
Current
consumption from I/O power supply |
50 mA/CN max. | |
Weight | 150 g max. | Cable length | Line driver outputs: 10 m max.
Other I/O: 3 m max. |
|
Circuit layout | ![]() |
|||
Installation orientation
and restrictions |
Installation orientation:
• Connected to a CPU Unit: Possible in upright installation. • Connected to a Communications Coupler Unit: Possible in 6 orientations. Restrictions: The number of external inputs that can be always ON is restricted as shown below. ![]() |
|||
Terminal connection
diagram |
![]() |
|||
Failure detection | None | Protection | None |
Unit name | Pulse Output Unit | Model | NX-PG0342-5 | |
---|---|---|---|---|
Number of channels | 4 channels | Type of external
connections |
MIL connector (34 terminals ×2) | |
I/O refreshing method *1 | Synchronous I/O refreshing or task period prioritized refreshing | |||
Indicators | ![]() |
I/O signals | Inputs: 5 per channel. External
inputs *2 Outputs: 5 per channel. 1 forward direction pulse output, 1 reverse direction pulse output, and 3 external outputs (per channel) *3 |
|
Control method | Open-loop control through pulse string output | |||
Controlled drive | Servo drive with a pulse string input or a stepper motor drive | |||
Pulse output form | Line driver output | |||
Unit of control | Pulses | |||
Maximum pulse output
speed |
4 Mpps | |||
Pulse output method | Forward/reverse direction pulse outputs, Pulse + direction outputs, or Phase
differential pulse output multiplication x1/2/4 |
|||
Position control range | -2,147,483,648 to 2,147,483,647 pulses | |||
Velocity control range | 1 to 4,000,000 pps | |||
Positioning *4 | ||||
Single-axis position
control |
Absolute positioning, relative positioning, and interrupt feeding | |||
Single-axis velocity
control |
Velocity control (velocity feeding in Position Control Mode) | |||
Single-axis
synchronized control |
Cam operation and gear operation | |||
Single-axis manual
operation |
Jogging | |||
Auxiliary function for
single-axis control |
Homing, stopping, and override changes | |||
External input specifications (except for line receiver inputs) | ||||
Input voltage | 21.6 to 26.4 VDC
(24 VDC +10%, -10%) |
ON voltage/
ON current |
15 VDC min./3 mA min. | |
Input current | 4.6 mA typical (24 VDC) | OFF voltage/OFF
current |
4.0 VDC max./1 mA max. | |
ON/OFF response time | External inputs 0 and 1: 1 μs max./2 μs max.
External inputs 2 to 4: 20 μs max./400 μs max. |
|||
Internal I/O common
processing |
PNP | |||
External input specifications (line receiver inputs) | ||||
Input voltage | EIA standard RS-422-A line
driver levels |
High level input voltage | VIT+: 0.1 V min. | |
Input impedance | 120 Ω ± 5% | Low level input voltage | VIT-: -0.1 V max. | |
Hysteresis voltage | Vhys (VIT+ - VIT-): 60 mV | |||
Line driver output specifications | ||||
Output voltage | RS-422-A line driver level (equivalent to AM26C31) | |||
Maximum load current | 20 mA | |||
Maximum output
frequency |
4 Mpps | |||
External output specifications | ||||
Rated voltage | 24 VDC | |||
Load voltage range | 15 to 28.8 VDC | Residual voltage | 1.0 V max. | |
Maximum load current | 30mA | Leakage current | 0.1 mA max. | |
ON/OFF response time | External output 0: 5 μs max./200 μs max.
External outputs 1 and 2: 0.5 ms max./1 ms max. |
|||
Internal I/O common
processing |
PNP | |||
Dimensions |
30 × 100 × 71 mm (W×H×D) |
Isolation
method |
External inputs: Photocoupler isolation
External outputs: Digital isolator |
|
Insulation resistance | 20 MΩ min. between isolated
circuits (at 100 VDC) |
Dielectric
strength |
510 VAC between isolated circuits
for 1 minute at a leakage current of 5 mA max. |
|
I/O power supply source |
Supply from external source
(24 VDC +20%, -15%) |
Current capacity
of I/O power supply terminals |
Without I/O power supply terminals | |
NX Unit power
consumption |
• Connected to a CPU Unit
1.65 W max. • Connected to a Communi- cations Coupler Unit 1.30 W max. |
Current
consumption from I/O power supply |
50 mA/CN max. | |
Weight | 150 g max. | Cable length | Line driver outputs: 10 m max.
Other I/O: 3 m max. |
|
Circuit layout | ![]() |
|||
Installation orientation
and restrictions |
Installation orientation:
• Connected to a CPU Unit: Possible in upright installation. • Connected to a Communications Coupler Unit: Possible in 6 orientations. Restrictions: The number of external inputs that can be always ON is restricted as shown below. ![]() |
|||
Terminal connection
diagram |
![]() |
|||
Failure detection | None | Protection | None |
Refer to the user's manual for the CPU Unit details on the CPU Units to which NX Units can be connected.
NX Unit | Corresponding unit versions/versions | ||
---|---|---|---|
Model | Unit version | CPU Unit | Sysmac Studio |
NX-PG0112 | Ver. 1.1 | Ver.1.13 | Ver. 1.17 |
Ver. 1.2 | |||
Ver. 1.3 | Ver. 1.19 | ||
NX-PG0122 | Ver. 1.0 | Ver.1.13 | Ver. 1.17 |
Ver. 1.1 | |||
Ver. 1.2 | |||
Ver. 1.3 | Ver. 1.19 | ||
NX-PG0232-5 | Ver. 1.2 | Ver.1.13 | Ver. 1.17 |
Ver. 1.3 | Ver. 1.19 | ||
NX-PG0242-5 | Ver. 1.2 | Ver.1.13 | Ver. 1.17 |
Ver. 1.3 | Ver. 1.19 | ||
NX-PG0332-5 | Ver. 1.2 | Ver.1.13 | Ver. 1.17 |
Ver. 1.3 | Ver. 1.19 | ||
NX-PG0342-5 | Ver. 1.2 | Ver.1.13 | Ver. 1.17 |
Ver. 1.3 | Ver. 1.19 |
Note: Some Units do not have all of the versions given in the above table. If a Unit does not have the specified version, support is provided by the oldest available version after the specified version. Refer to the user’s manuals for the specific Units for the relation between models and versions.
NX Unit | Corresponding unit versions/versions | |||
---|---|---|---|---|
Model | Unit version | EtherCAT
Coupler Unit |
CPU Unit or Industrial PC | Sysmac Studio |
NX-PG0112 | Ver. 1.1 | Ver. 1.0 | Ver. 1.05 | Ver. 1.10 |
Ver. 1.2 | Ver. 1.3 *2*4 | Ver. 1.13 | ||
Ver. 1.3 | Ver. 1.19 | |||
NX-PG0122 | Ver. 1.0 | Ver. 1.0 | Ver. 1.05 | Ver. 1.06 |
Ver. 1.1 | Ver. 1.08 | |||
Ver. 1.2 | Ver. 1.3 *2*4 | Ver. 1.13 | ||
Ver. 1.3 | Ver. 1.19 | |||
NX-PG0232-5 | Ver. 1.2 | Ver. 1.3 *2*4 | Ver. 1.05 | Ver. 1.15 |
Ver. 1.3 | Ver. 1.19 | |||
NX-PG0242-5 | Ver. 1.2 | Ver. 1.3 *2*4 | Ver. 1.05 | Ver. 1.15 |
Ver. 1.3 | Ver. 1.19 | |||
NX-PG0332-5 | Ver. 1.2 | Ver. 1.3 *2*4 | Ver. 1.05 | Ver. 1.15 |
Ver. 1.3 | Ver. 1.19 | |||
NX-PG0342-5 | Ver. 1.2 | Ver. 1.3 *2*4 | Ver. 1.05 | Ver. 1.15 |
Ver. 1.3 | Ver. 1.19 |
Note: Some Units do not have all of the versions given in the above table. If a Unit does not have the specified version, support is provided by the oldest available version after the specified version. Refer to the user’s manuals for the specific Units for the relation between models and versions.
*1. You can use the following versions if time stamp refreshing is not used.
*2. To use task period prioritized refreshing, you must use the NX-ECC203.
*3. If you do not use task period prioritized refreshing, you can use EtherCAT Coupler Units which support Position Interface Units with unit version 1.1 or earlier.
*4. If you do not use task period prioritized refreshing, you can use EtherCAT Coupler Units with unit version 1.0.
NX Unit | Corresponding unit versions/versions | ||||||
---|---|---|---|---|---|---|---|
Model | Unit
version |
Application with an NJ/NX/NY-series Controller
*1 |
Application with a CS/CJ/CP-series PLC *2 | ||||
EtherNet/IP
Coupler Unit |
CPU Unit or
Industrial PC |
Sysmac
Studio |
EtherNet/IP
Coupler Unit |
Sysmac
Studio |
NX-IO
Configurator *3 |
||
NX-PG0112 | Ver. 1.1 | --- | --- | --- | --- | --- | --- |
Ver. 1.2 | |||||||
Ver. 1.3 | |||||||
NX-PG0122 | Ver. 1.0 | --- | --- | --- | --- | --- | --- |
Ver. 1.1 | |||||||
Ver. 1.2 | |||||||
Ver. 1.3 | |||||||
NX-PG0232-5 | Ver. 1.2 | --- | --- | --- | --- | --- | --- |
Ver. 1.3 | |||||||
NX-PG0242-5 | Ver. 1.2 | --- | --- | --- | --- | --- | --- |
Ver. 1.3 | |||||||
NX-PG0332-5 | Ver. 1.2 | --- | --- | --- | --- | --- | --- |
Ver. 1.3 | |||||||
NX-PG0342-5 | Ver. 1.2 | --- | --- | --- | --- | --- | --- |
Ver. 1.3 |
Note: 1. Some Units do not have all of the versions given in the above table. If a Unit does not have the specified version, support is provided by the oldest available version after the specified version. Refer to the user’s manuals for the specific Units for the relation between models and versions.
Note: 2. You cannot connect the relevant NX Unit or use the relevant NX Unit function if “---” is shown in the corresponding unit versions/versions column.
*1. Refer to the user's manual of the EtherNet/IP Coupler Unit for the unit versions of EtherNet/IP Units corresponding to EtherNet/IP Coupler Units.
*2. Refer to the user's manual of the EtherNet/IP Coupler Unit for the unit versions of CPU Units and EtherNet/IP Units corresponding to EtherNet/IP Coupler Units.
*3. For connection to an EtherNet/IP Coupler Unit with unit version 1.0, connection is supported only for a connection to the peripheral USB port on the EtherNet/IP Coupler Unit. You cannot connect by any other path. If you need to connect by another path, use an EtherNet/IP Coupler Unit with unit version 1.2 or later.
last update: February 6, 2020