E9NC-AA / VA

IoT Status Monitoring Amplifier

E9NC-AA / VA

IoT Status Monitoring Amplifiers for General-purpose Analog Outputs Are Connectable to Various Sensors

Ratings and specifications

Item Types Current input Voltage input
Model for Sensor Communications Unit *1
NPN output E9NC-AA10 E9NC-AA0 E9NC-VA10 E9NC-VA0
PNP output E9NC-AA40 E9NC-VA40
connection
method
Connector for
Sensor
Communications
Unit Pre-wired (2 m)
Connector for
Sensor
Communications
Unit
Connector for
Sensor
Communications
Unit Pre-wired (2 m)
Connector for
Sensor
Communications
Unit
Output 1 output *2 2 outputs *3 1 output *2 2 outputs *3
Power supply voltage 24 VDC (20.4 to 26.4 V) class2 power is supplied from the connector via the communication
unit.
Power consumption 24 V power supply voltage in normal mode: 1,080 mW or less (consumption current 45 mA
max.), eco-function ON: 840 mW or less (consumption current 35 mA max.), and eco-function
LO: 960 mW or less (consumption current 40 mA max.)
Sensor
input
range
Voltage
range
4 to 20 mA DC 1 to 5 VDC
Input
impedance
204 kΩ±1% (Input: no-insulated)
Repeatability F.S./
25°C
±0.2% F.S.
Display accuracy F.S. ±0.5% F.S. ±2digit
Temperature
characteristics F.S.
±1% F.S.
Control output Load power supply
voltage:
24 VDC (20.4 to 26.4 V)
class2,
open collector output
type
Load current:
100 mA max. for 1 to 3
units use, 20 mA max.
for 4 or more units
connected
Residual voltage:
Load current less than
10 mA: 1 V max.,
Load current 10 to 100
mA: 2 V max.
Off-state current: 0.1
mA max.
Refer to the
communication
unit specifications
Load power supply
voltage:
24 VDC (20.4 to 26.4 V)
class2,
open collector output
type
Load current:
100 mA max. for 1 to 3
units use, 20 mA max.
for 4 or more units
connected
Residual voltage:
Load current less than
10 mA: 1 V max.,
Load current 10 to 100
mA: 2 V max.
Off-state current: 0.1
mA max.
Refer to the
communication
unit specifications
Response Time 1/10/100/500ms/1/10/30/60s (Initial value 500 ms)
Indicator Seven Segment Display (both sub and main digital display: white)
OUT indictor (orange), NO/NC indicator (orange), ST indicator (blue), zero-reset indicator
(green)
OUT selective indicator (orange) (two lamps only)
Protection circuit Power supply reverse
connection protection,
output short-circuit
protection, and output
reverse connection
protection
Power supply
reverse connection
protection,
output short-
circuit protection
Power supply reverse
connection protection,
output short-circuit
protection, and output
reverse connection
protection
Power supply
reverse connection
protection,
output short-
circuit protection
Sensitivity adjustment Smart Tuning (2-point tuning, full auto tuning, or percentage tuning (-99% to 99%)) or manual
adjustment
Maximum connectable
Units
16 Units Model E3NW-ECT
*4,
30 units when used
Model E3NW-CCL,
16 units when used
16 Units Model E3NW-ECT
*4,
30 units when used
Model E3NW-CCL,
16 units when used
No. of Units for mutual
interference prevention
None
Functions Operation
mode
NO (Normal Open)/NC (Normal Close)
Zero Reset Yes
Timer Select from timer disabled, OFF delay, ON delay, or One-shot timer
1 ms to 9999 ms
Scaling Set the upper/lower limits (-1999.9999 to 9999.9999, min. unit: 0.001)
Resetting
settings *5
Select from initial reset (factory defaults) or user reset (saved settings).
Eco mode Select from OFF (digital display lit), Eco ON (digital display not lit), and Eco LO (digital display
dimmed).
Bank
switching
Select from banks 1 to 4.
Output 1
Settings
Select from Normal detection mode or Wind comparator (area) detection mode.
Output 2
Settings
--- Select from Normal
detection mode,
Wind comparator
(area) detection
mode, and Error
output mode.
--- Select from Normal
detection mode,
Wind comparator
(area) detection
mode, and Error
output mode.
Hysteresis
width
Select from standard setting or user setting. For a user setting, the hysteresis width can be
set from 0 to 9999.9999.
Display
switch
Select from normal display, peak/bottom display, or CH number display (setting value display
when adjusting the threshold)
Key Lock Yes
Ambient temperature
range and supply
current for sensor
head
Operating:
Sensor consumption current 40 mA max.
Groups of 1 or 2 Amplifier Units: 0 to 55°C,
Groups of 3 to 10 Amplifier Units: 0 to 50°C,
Groups of 11 to 16 Amplifier Units: 0 to 45°C,
Groups of 17 to 30 Amplifier Units: 0 to 40°C *6
Sensor consumption current 100 mA max.
1 unit: 0 to 55°C, Groups of 2 to 7 Amplifier Units: 0 to 50°C, Groups of 8 to 12 Amplifier
Units: 0 to 45°C
Sensor consumption current 200 mA:
1 unit: 0 to 55°C, Groups of 2 to 5 Amplifier Units: 0 to 50°C
Storage: -30 to +70°C (with no icing or condensation)
Ambient humidity range Operating and storage: 35% to 85% RH (with no condensation)
Height 2,000 m max.
Installation
environment
Pollution level 3 (according to IEC60947-1)
Insulation resistance 20 MΩ min. (at 500 VDC)
Dielectric strength 1,000 VAC 50/60Hz 1min
Vibration resistance 10 to 55 Hz with a 1.5-mm double amplitude for 2 hrs each in X, Y and Z directions
Shock resistance 150 m/s2 for 3 times each in X, Y and Z directions
Degree of protection
(Sensor Head)
IEC60529 IP50
Weight (packed state/
sensor)
Approx. 95 g/
Approx. 45 g
Approx. 65 g/
Approx. 25 g
Approx. 95 g/
Approx. 45 g
Approx. 65 g/
Approx. 25 g
Materials Case Polycarbonate (PC)
Cover Polycarbonate (PC)
Code Polyvinyl chloride (PVC)
Accessories Manual, 6-pin plug connector for connecting ECON cable (model XN2A-1670) x 1

*1. The communication unit is compatible with EtherCAT type E3NW-ECT and E3NW-CCL of CC-Link. This unit is not usable
      with E3NW-CRT.
*2. Channel 1 of each amplifier unit is output as the output drawn by the cord.
*3. Output signals from two sensors are assigned to the PLC via the network. Various settings can be changed and detected
      values can be read by operating the PLC via the network.
*4. This is the case of connecting with OMRON NJ series. For details, refer to the communication unit manual.
*5. The bank is not reset by the user reset function or saved by the user save function.
*6. Only E9NC-VA0/AA0 is able to connect to between 17 and 30 units.