Master Control Units (S-Controllers)
* Information in this page is a reference that you created on the basis of information in the product catalog before the end of production, may be different from the current situation, such as goods for / supported standards options / price / features of the product. Before using, please check the compatibility and safety system.
last update: November 27, 2013
Number of I/O points | 256 points (128 inputs/128 outputs)
128 points (64 inputs/64 outputs) Selectable by DM setting. The default setting is 256 points. |
---|---|
Max. number of Slaves
per Master |
256 points: 32
128 points: 16 |
I/O words | Input words: 000 to 007
Output words: 010 to 017 |
Programming language | Ladder diagram |
Types of instruction | 14 basic and 81 special instructions (125 instructions in total) |
Execution time | LD instruction: 0.97 μs
MOV instruction: 9.1 μs |
Program capacity | 4,096 words |
Data memory | 2,022 + 512 (read-only) words |
Timers/Counters | 128 timers/counters |
Work bits | 640 bits |
Memory backup | Flash memory (without battery): User programs
Lithium battery: Data memory etc. (Battery life: 10 years min. at an ambient temperature of 25°C.) |
Peripheral port | 1 point |
RS-232C port | 1 point (SRM1-C02 only)
Host Link, NT Link, 1:1 Link, or no protocol |
Programming tool | Programming Consoles: CQM1-PRO01-E, C200H-PRO27-E
CX-Programmer (Supported for versions 2 or later.) WS02-CXP1-E SYSMAC Support Software (MS-DOS version): C500-ZL3AT1-E |
Communications method | CompoBus/S protocol | |
---|---|---|
Coding method | Manchester coding method | |
Connection method | Multi-drop method and T-branch method *1 | |
Communications baud rate | 750,000 bps/93,750 bps *2 | |
Commu-
nications cycle time |
High-speed
communications mode |
0.5 ms with 8 Slaves for inputs and 8 Slaves for outputs |
0.8 ms with 16 Slaves for inputs and 16 Slaves for outputs | ||
Long-distance
communications mode |
4.0 ms with 8 Slaves for inputs and 8 Slaves for outputs | |
6.0 ms with 16 Slaves for inputs and 16 Slaves for outputs | ||
Communications cable | 2-conductor VCTF cable (0.75 x 2), 4-conductor VCTF cable (0.75 x 4)
Dedicated flat cable |
|
Commu-
nications distance |
High-speed
communications mode |
2-conductor VCTF cable:
Main line length: 100 m max. Branch line length: 3 m max. Total branch line length: 50 m max. Flat cable, 4-conductor VCTF cable: Main line length: 30 m max. Branch line length: 3 m max. Total branch line length: 30 m max. (When flat cable is used to connect fewer than 16 Slaves, the main line can be up to 100 m long and the total branch line length can be up to 50 m.) |
Long-distance
communications mode |
2-conductor VCTF cable:
Main line length: 500 m max. Branch line length: 6 m max. Total branch line length: 120 m max. Flat cable, 4-conductor VCTF cable: Variable branch wiring (total cable length 200 m max.) (There are no limits on the branching format or main, branch, or total line lengths. The terminator must be connected to the point in the system farthest from the master.) |
|
Max. number of connecting nodes | 32 | |
Error control checks | Manchester code check, frame length check, and parity check |
*1. A terminator must be connected to the point in the system farthest from the Master.
*2. The communications baud rate is switched using DM settings (default setting is 750,000 bps).
Supply voltage | 24 VDC |
---|---|
Allowable supply voltage | 20.4 to 26.4 VDC |
Power consumption | 3.5 W max. |
Inrush current | 12.0 A max. |
Noise immunity | Conforms to IEC61000-4-4, 2 kV (power lines) |
Vibration resistance | 10 to 57 Hz, 0.075-mm amplitude, 57 to 150 Hz, acceleration: 9.8 m/s2 in X, Y, and Z
directions for 80 minutes each (Time coefficient; 8 minutes × coefficient factor 10 = total time 80 minutes) |
Shock resistance | 147 m/s2 three times each in X, Y, and Z directions |
Ambient temperature | Operating: 0°C to 55°C
Storage: -20°C to 75°C |
Humidity | 10% to 90% (with no condensation) |
Atmosphere | Must be free from corrosive gas. |
Terminal screw size | M3 |
Power interrupt time | DC type: 2 ms min. |
Weight | 150 g max. |
last update: November 27, 2013