Bi-power Relays
last update: November 18, 2024
Item | Rated current
(mA) |
Coil
resist- ance (Ω) |
Coil inductance (H) | Must-
operate voltage (V) |
Must-
release voltage (V) |
Maximum
voltage (V) |
Power
con- sumption (VA, W) |
|||
---|---|---|---|---|---|---|---|---|---|---|
Rated
voltage (V) |
50 Hz | 60Hz | Armature
OFF |
Armature
ON |
||||||
AC | 12 | 106.5 | 91 | 46 | 0.17 | 0.33 | 80% max.
*1 |
30% min.
*2 |
110% of
rated voltage |
Approx. 1.0
to 1.2 (at 60 Hz) |
24 | 53.8 | 46 | 180 | 0.69 | 1.3 | |||||
100/110 | 11.7/12.9 | 10/11 | 3,750 | 14.54 | 24.6 | Approx. 0.9
to 1.1 (at 60 Hz) |
||||
110/120 | 9.9/10.8 | 8.4/9.2 | 4,430 | 19.2 | 32.1 | |||||
200/220 | 6.2/6.8 | 5.3/5.8 | 12,950 | 54.75 | 94.07 | |||||
220/240 | 4.8/5.3 | 4.2/4.6 | 18,790 | 83.5 | 136.4 | |||||
DC | 6 | 150 | 40 | 0.16 | 0.33 | 10% min.
*2 |
Approx. 0.9 | |||
12 | 75 | 160 | 0.73 | 1.37 | ||||||
24 | 36.9 | 650 | 3.2 | 5.72 | ||||||
48 | 18.5 | 2,600 | 10.6 | 21.0 | ||||||
100/110 | 9.1/10 | 11,000 | 45.6 | 86.2 |
Item | Rated current
(mA) |
Coil
resist- ance (Ω) |
Coil inductance (H) | Must-
operate voltage (V) |
Must-
release voltage (V) |
Maximum
voltage (V) |
Power
con- sumption (VA, W) |
|||
---|---|---|---|---|---|---|---|---|---|---|
Rated
voltage (V) |
50 Hz | 60Hz | Armature
OFF |
Armature
ON |
||||||
AC | 12 | 159 | 134 | 24 | 0.12 | 0.21 | 80% max.
*1 |
30% min.
*2 |
110% of
rated voltage |
Approx.
1.6 to 2.0 (at 60 Hz) |
24 | 80 | 67 | 100 | 0.44 | 0.79 | |||||
100/110 | 14.1/16 | 12.4/13.7 | 2,300 | 10.5 | 18.5 | |||||
200/220 | 9.0/10.0 | 7.7/8.5 | 8,650 | 34.8 | 59.5 | |||||
DC | 12 | 112 | 107 | 0.45 | 0.98 | 10% min.
*2 |
Approx. 1.4 | |||
24 | 58.6 | 410 | 1.89 | 3.87 | ||||||
48 | 28.2 | 1,700 | 8.53 | 13.9 | ||||||
100/110 | 12.7/13 | 8,500 | 29.6 | 54.3 |
Item | Rated current
(mA) |
Coil
resist- ance (Ω) |
Coil inductance (H) | Must-
operate voltage (V) |
Must-
release voltage (V) |
Maximum
voltage (V) |
Power
con- sumption (VA, W) |
|||
---|---|---|---|---|---|---|---|---|---|---|
Rated
voltage (V) |
50 Hz | 60Hz | Armature
OFF |
Armature
ON |
||||||
AC | 12 | 199 | 170 | 20 | 0.1 | 0.17 | 80% max.
*1 |
30% min.
*2 |
110% of
rated voltage |
Approx.
1.95 to 2.5 (at 60 Hz) |
24 | 93.6 | 80 | 78 | 0.38 | 0.67 | |||||
100/110 | 22.5/25.5 | 19/21.8 | 1,800 | 10.5 | 17.3 | |||||
200/220 | 11.5/13.1 | 9.8/11.2 | 6,700 | 33.1 | 57.9 | |||||
DC | 12 | 120 | 100 | 0.39 | 0.84 | 10% min.
*2 |
Approx. 1.5 | |||
24 | 69 | 350 | 1.41 | 2.91 | ||||||
48 | 30 | 1,600 | 6.39 | 13.6 | ||||||
100/110 | 15/15.9 | 6,900 | 32.0 | 63.7 |
Classification | 1 pole | Double-, 3-, and 4-pole
models |
Bifurcated contacts | |||||
---|---|---|---|---|---|---|---|---|
Load | Resistive
load |
Inductive load
(cos φ = 0.4, L/R = 7 ms) |
Resistive
load |
Inductive load
(cos φ = 0.4, L/R = 7 ms) |
Resistive
load |
Inductive load
(cos φ = 0.4, L/R = 7 ms) |
||
Contact type | Single | Bifurcated | ||||||
Contact
materials |
Ag alloy | Ag | ||||||
Rated load | 15 A at 110 VAC
15 A at 24 VDC |
10 A at 250 VAC | 10 A at 110 VAC
7 A at 24 VDC |
10 A at 110 VAC
10 A at 24 VDC |
10 A at 250 VAC | 7.5 A at 110 VAC
5 A at 24 VDC 5 A at 24 VDC |
5 A at 110 VAC
5 A at 24 VDC |
4 A at 110 VAC
4 A at 24 VDC |
Electrical endurance*1 | 200,000
operations min. |
200,000
operations min. |
200,000
operations min. |
3-, 4-pole: 200,000 operations min.
2-pole: 500,000 operations min. |
50,000
operations min. |
3-, 4-pole: 200,000 operations min.
2-pole: 500,000 operations min. |
2-pole: 500,000 operations min. | |
Rated carry
current |
15 A | 10 A | 7 A | |||||
Maximum
contact voltage |
250 VAC
125 VDC |
250 VAC
125 VDC |
250 VAC
125 VDC |
|||||
Maximum
contact current |
15 A | 10 A | 7 A |
Type | Single-pole and double-pole models
(standard models and bifurcated contact models) |
Single-pole, double-pole models
(models with built-in operation indicators, models with built-in diodes, and models with built-in CR circuits), 3-pole and 4-pole models |
---|---|---|
Ambient operating
temperature |
-25 to 55°C
(with no icing or condensation) *2 |
-25 to +40°C
(with no icing or condensation) *3 |
Ambient operating
humidity |
5% to 85% |
Type | Standard models, models with
built-in operation indicators, models with built-in CR circuits, and models with built-in diodes |
Bifurcated contacts | |
---|---|---|---|
Contact resistance *1 | 50 mΩ max. | ||
Operating time *2 | 25 ms max. | ||
Release time *2 | 25 ms max. | ||
Maximum
operating frequency |
Mechanical | 18,000 operations/h | |
Rated load | 1,800 operations/h | ||
Insulation resistance *3 | 100 MΩ min. | ||
Dielectric
strength |
Between coil and
contacts |
2,000 VAC at 50/60 Hz for 1 min. | |
Between contacts
of different polarity |
|||
Between contacts
of the same polarity |
1,000 VAC at 50/60 Hz for 1 min. | ||
Vibration
resistance |
Destruction | 10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude) | |
Malfunction | 10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude) | ||
Shock
resistance |
Destruction | 1,000 m/s2 | |
Malfunction | 200 m/s2 | ||
Endurance | Mechanical | AC: 50,000,000 operations min.
DC: 100,000,000 operations min. (switching frequency: 18,000 operations/h) |
|
Failure rate P value
(reference value) *4 |
100 mA at 5 VDC | 10mA at 5 VDC | |
Weight | 1-pole and 2-pole: 40 g, 3-pole: Approx. 50 g, 4-pole: Approx. 70 g |
Item | LY1, 100 VAC | LY2, 100 VAC | ||||
---|---|---|---|---|---|---|
Load type | Conditions | Operating
frequency |
Electrical life
(×10,000 operations min.) |
Conditions | Operating
frequency |
Electrical life
(×10,000 operations min.) |
AC motor | 400 W, 100 VAC
single-phase with 35-A inrush current, 7-A current flow |
ON for 10 s,
OFF for 50 s |
5 | 200 W, 100 VAC
single-phase with 25-A inrush current, 5-A current flow |
ON for 10 s,
OFF for 50 s |
20 |
AC lamp | 300 W, 100 VAC
with 51-A inrush current, 3-A current flow |
ON for 5 s,
OFF for 55 s |
10 | 300 W, 100 VAC
with 51-A inrush current, 3-A current flow |
ON for 5 s,
OFF for 55 s |
8 |
500 W, 100 VAC
with 78-A inrush current, 5-A current flow |
2.5 | |||||
Capacitor
(2,000 μF) |
24 VDC with 50-A
inrush current, 1-A current flow |
ON for 1 s,
OFF for 6 s |
10 | 24 VDC with 50-A
inrush current, 1-A current flow |
ON for 1 s,
OFF for 15 s |
1 |
24 VDC with 20-A
inrush current, 1-A current flow |
15 | |||||
AC solenoid | 50 VA with 2.5-A
inrush current, 0.25-A current flow |
ON for 1 s,
OFF for 2 s |
150 | 50 VA with 2.5-A
inrush current, 0.25-A current flow |
ON for 1 s,
OFF for 2 s |
100 |
100 VA with 5-A
inrush current, 0.5-A current flow |
80 | 100 VA with 5-A
inrush current, 0.5-A current flow |
50 |
Item | LY4, 100 VAC | ||
---|---|---|---|
Load type | Conditions | Operating frequency | Electrical life
(×10,000 operations min.) |
AC motor | 200 W, 200 VAC three-phase with 5-A
inrush current, 1-A current flow |
ON for 10 s,
OFF for 50 s |
50 |
750 W, 200 VAC three-phase with 18-A
inrush current, 3.5-A current flow |
7 | ||
AC lamp | 300 W, 100 VAC with 51-A inrush current,
3-A current flow |
ON for 5 s,
OFF for 55 s |
5 |
Capacitor
(2,000 μF) |
24 VDC with 50-A inrush current,
1-A current flow |
ON for 1 s,
OFF for 15 s |
0.5 |
24 VDC with 20-A inrush current,
1-A current flow |
ON for 1 s,
OFF for 2 s |
20 | |
AC solenoid | 50 VA with 2.5-A inrush current,
0.25-A current flow |
ON for 1 s,
OFF for 2 s |
100 |
100 VA with 5-A inrush current,
0.5-A current flow |
50 |
• Standard models are certified for the UL and CSA safety standards.
• Refer to Model Number Structure on Lineup for a list of applicable models.
• The rated values for safety standard certification are not the same as individually defined performance values. Always check the specifications before use.
Model | Coil ratings | Number of
poles |
Contact ratings | Certified number of operations |
---|---|---|---|---|
LY | 6 to 240VAC
6 to 125VDC |
1 | 15A, 120VAC (General use) | 100,000 operations |
15A, 240VAC (General use) | 6,000 operations | |||
15A, 30VDC (Resistive) | ||||
1/2HP, 120VAC | 100,000 operations | |||
8.5FLA, 30LRA, 120VAC | ||||
TV-5, 120VAC | 25,000 operations | |||
470VA, Pilot duty, 120VAC | 6,000 operations | |||
6 to 240VAC
6 to 125VDC |
2 | 15A, 120VAC (General use) | 100,000 operations | |
12A, 240VAC (General use) | 6,000 operations | |||
7A, 250VAC (General use) | ||||
15A, 30VDC (Resistive) | ||||
5A, 38VDC (Resistive) | ||||
1/2HP, 120VAC | 100,000 operations | |||
1/3HP, 240VAC | 1,000 operations | |||
8.5FLA, 30LRA, 120VAC | 100,000 operations | |||
5FLA, 50LRA, 50VDC | ||||
TV-3, 120VAC | 25,000 operations | |||
345VA, Pilot duty, 120-240VAC | 6,000 operations | |||
B300/R300 | ||||
6 to 240VAC
6 to 125VDC |
3
4 |
10A, 240VAC (General use) (Same polarity) | 6,000 operations | |
10A, 30VDC (General use) (Same polarity) | ||||
2A, 40VDC (Resistive) (Same polarity) | ||||
1/2HP, 240VAC | 1,000 operations | |||
0.6A, 100VDC (Resistive) (Same polarity) | 6,000 operations |
Model | Coil ratings | Number of
poles |
Contact ratings | Certified number of operations |
---|---|---|---|---|
LY | 6 to 240VAC
6 to 125VDC |
1 | 15A, 120VAC (General use) | 100,000 operations |
15A, 240VAC (General use) | 6,000 operations | |||
15A, 30VDC (Resistive) | ||||
1/2HP, 120VAC | 100,000 operations | |||
8.5FLA, 30LRA, 120VAC | ||||
TV-5, 120VAC | 25,000 operations | |||
470VA, Pilot duty, 120VAC | 6,000 operations | |||
6 to 240VAC
6 to 125VDC |
2 | 15A, 120VAC (General use) | 6,000 operations | |
12A, 240VAC (General use) | ||||
7A, 250VAC (General use) | ||||
15A, 30VDC (Resistive) | ||||
5A, 38VDC (Resistive) | ||||
1/2HP, 120VAC | 100,000 operations | |||
1/3HP, 240VAC | 1,000 operations | |||
8.5FLA, 30LRA, 120VAC | 100,000 operations | |||
5FLA, 50LRA, 50VDC | ||||
TV-3, 120VAC | 25,000 operations | |||
345VA, Pilot duty, 120-240VAC | 6,000 operations | |||
B300/R300 Pilot duty | ||||
6 to 240VAC
6 to 125VDC |
3
4 |
10A, 240VAC (General use) (Same polarity) | 6,000 operations | |
10A, 30VDC (Resistive) (Same polarity) | ||||
1/8HP, 240VAC (Same polarity) | 1,000 operations | |||
1/2HP, 240VAC (Same polarity) | ||||
1/3HP, 240VAC (Same polarity) | ||||
2A, 40VDC (Resistive) | 6,000 operations | |||
0.6A, 100VDC (Resistive) |
Model | Coil ratings | Number of poles | Contact ratings | Certified number of operations |
---|---|---|---|---|
LY[] | 6 to 240 VAC
6 to 110 VDC |
1 | 15 A, 110 VAC resistive load | 200,000 operations |
10 A, 110 VAC inductive load | ||||
10 A, 250 VAC resistive load | ||||
7A, 250 VAC inductive load | ||||
10 A, 30 VDC resistive load | ||||
7 A, 30 VDC inductive load | ||||
6 to 240 VAC
6 to 125 VDC |
2 | 10 A, 250 VAC resistive load | 50,000 operations | |
10 A, 110 VAC resistive load | 200,000 operations | |||
7.5A, 110 VAC inductive load | ||||
7A, 250 VAC resistive load | ||||
4 A, 250 VAC inductive load | ||||
7 A, 30 VDC resistive load | ||||
4 A, 30 VDC inductive load | ||||
6 to 240 VAC
6 to 110 VDC |
3 | 10 A, 250 VAC resistive load | 50,000 operations | |
10 A, 110 VAC resistive load | 100,000 operations | |||
7.5A, 110 VAC inductive load | ||||
6 to 240 VAC
6 to 125 VDC |
4 | 10 A, 250 VAC resistive load | 50,000 operations | |
10 A, 110 VAC resistive load | 100,000 operations | |||
7.5A, 110 VAC inductive load |
• When ordering a model that is certified for VDE or Lloyd’s Register (LR) standards, always specify “VDE-certified Model” or “LR Standard-certified Model” with your order.
Model | Coil ratings | Number of poles | Contact ratings | Certified number of operations |
---|---|---|---|---|
LY[]-VD | 6, 12, 24, 50,
110, or 220 VAC 6, 12, 24, 48, or 110 VDC |
1 | 10 A, 220 VAC resistive load | 200,000 operations |
7 A, 220 VAC inductive load | ||||
10 A, 28 VDC resistive load | ||||
7 A, 28 VDC inductive load | ||||
2 | 7 A, 220 VAC resistive load | |||
4 A, 220 VAC inductive load | ||||
7 A, 28 VDC resistive load | ||||
4 A, 28 VDC inductive load |
Model | Coil ratings | Number of poles | Contact ratings |
---|---|---|---|
LY[] | 6 to 240 VAC
6 to 110 VDC |
2 | 7.5 A, 230 VAC inductive load |
4 | 5 A, 24 VDC inductive load |
Model | Ratings | Listed/Recognized |
---|---|---|
PTF-08-PU | 10A 250V | Recognized |
PTF-14-PU | 10A 250V (Same polarity) | |
PTFZ-08-E | 15A 250V (at 50 deg)
12A 250V (at 70 deg) |
|
PTFZ-14-E | ||
PTF08A
PT08 |
15A 250V | |
PTF11A
PTF14A PT11 PT14 |
10A 250V |
Model | Ratings | Class number |
---|---|---|
PTF-08-PU | 10A 250V | 3211 07 |
PTF-14-PU | 10A 250V (Same polarity) | |
PTFZ-08-E | 15A 250V (at 50 deg)
12A 250V (at 70 deg) |
|
PTFZ-14-E | ||
PTF08A | 15A 240V AC | |
PTF11A
PTF14A |
10A 240V AC |
Model | EMC Directive | Low Voltage Directive | Machinery Directive | Safety Category |
---|---|---|---|---|
PTFZ-08-E | Not applicable | ○ | Not applicable | 1 |
PTFZ-14-E | ||||
PTF-08-PU(-L) | ||||
PTF-14-PU(-L) |
Model | Ratings | Standard number | Certification number |
---|---|---|---|
PTF-08-PU | 10A 250V *1 | EN 61984 | R50327595 |
PTF-14-PU | 10A 250V *2 | ||
PTFZ-08-E | 15A 250V (at 50 deg)
12A 250V (at 70 deg) |
R50438680 | |
PTFZ-14-E |
*1. Ratings are for an ambient temperature of 55°C. At an ambient temperature of 70°C, the value is 7A.
*2. Ratings are for an ambient temperature of 40°C. At an ambient temperature of 70°C, the value is 7A.
All standard models comply with the Electrical Appliances and Material Safety Act.
Model | Coil ratings | Number of poles | Contact ratings |
---|---|---|---|
LY[] | 6 to 240 VAC
6 to 120 VDC |
1 | 15 A at 200 VAC |
2
3 4 |
10A at 200 VAC |
Model | Continuous
carry current |
Dielectric strength | Insulation
resistance *1 |
Remarks |
---|---|---|---|---|
PTF-[]-PU(L) | 10 A | Between contact terminals of same polarity: 2,000 VAC,
1 min |
1,000 MΩ
min. |
|
Between contact terminals of different polarity: 2,000 VAC,
1 min |
||||
Between coil and contact terminals: 2,000 VAC, 1 min | ||||
PTFZ-[][]-E | 12 A (@70°C)
15 A (@50°C) *2 |
Between contact terminals of different polarity: 2,500 VAC,
1 min |
1,000 MΩ
min. |
|
Between contact terminals of same polarity: 2,500 VAC,
1 min |
||||
Between ground terminals: 2,500 VAC, 1 min | ||||
Between coil and contact terminals: 2,500 VAC, 1 min | ||||
PTF[][]A | 10 A | Between terminals: 2,000 VAC for 1 min | 100 MΩ min. | |
PT-[][] | 10 A | Between terminals: 2,000 VAC for 1 min | 100 MΩ min. | |
PT[][]-0 | 10 A | Between terminals: 2,000 VAC for 1 min | 100 MΩ min. | |
PT[][]QN | 10 A | Between terminals: 2,000 VAC for 1 min | 100 MΩ min. |
last update: November 18, 2024