I/O power supply voltage | 20.4 to 26.4 VDC (24 VDC -15%/+10%) |
---|---|
Current consumption | 90 mA max. |
Connection distance | Total length: 3 m Maximum length between Units: 1 m |
Ambient operating temperature | -10°C to 55°C |
Ambient operating humidity | 25% to 85% (with no condensation) |
Weight | Approx. 250 g |
Dimensions | 110 x 60 x 65 mm (W x H x D) |
Accessories | I/O Unit Connecting Cable (40 mm) |
Output current | 0.5 A per point max. |
---|---|
Residual voltage | 1.2 V max. (0.5 A DC between each output terminal and G) |
Leakage current | 0.1 mA max. (24 VDC between each output terminal and G) |
ON delay time | 0.5 ms max. |
OFF delay time | 1.5 ms max. |
Number of circuits | 2 |
Number of counters | 1 | |
---|---|---|
Operating mode | Linear counter | |
Count input | Input signal | Encoder input (A, B, Z) |
Signal level | 24 VDC | |
Input type | Differential phase pulse input Pulse and direction input | |
Maximum counting speed | 50 kHz (kcps) | |
Counting range | -8,388,608 to +8,388,607 | |
Other | Differential phase pulse input can be set to a multiplication factor of 1 or 4. | |
External input | Input signal | External input (IN) |
Signal level | 24 VDC | |
External output | Output | 2 external outputs (OUT1 and OUT2) |
Maximum switching capacity | 24 VDC 0.5 A | |
Allocated words | IN | 3 words |
OUT | 3 words |